5
Firestop Supports are
currently manufactured for
pipe sizes of 3" through 12"
only. Larger sizes may be
locally fabricated from sheet
metal, provided that the
mandatory 1-inch clearance
is maintained, the pipe is
adequately supported, and the
installation is acceptable to
Local Authorities. In
multistory buildings, a Firestop/
Spacer must be provided at every
floor /ceiling level other than the
first floor which requires a support.
4. Wall Thimble. For a through-
the-wall system, install the Wall
Thimble, as shown in Figure 5. The
Wall Thimble is designed to ac-
commodate walls up to 6 inches
thick. If you have thicker walls, a
sleeve extension should be fabri-
cated and attached to the existing
sleeve . Do not fill the air space
between the B-vent Pipe Section
and the Wall Thimble with insula-
tion, although an RTV-type sealant
may be applied around the flange
and nail heads if desired.
5. Pipe Assembly. Sections of
Simpson Dura-Vent round pipe are
joined together by lining up the fe-
male end of the locking lug with the
male end slot, pushing them together,
and turning clockwise to twist lock.
Refer to Figure 9. Sheet metal
screws are not needed for 3" through
PIPE SIZE
STOCK NUMBER OF
CEILING SUPPORT
FRAMED INSIDE
DIMENSIONS (X & Y)
FIG 4
3 INCH 1440 7-3/8" X 7-3/8"
4 INCH 1441 7-3/8" X 7-3/8"
5 INCH 1442 9-1/8" X 9-1/8"
6 INCH 1443 9-1/8" X 9-1/8"
7 INCH 1444 11-1/8" X 11-1/8"
8 INCH 1445 11-1/8" X 11-1/8"
10 INCH 1446 13-1/8" X 13-1/8"
12 INCH 1447 13-1/8" X 13-1/8"
Table 1
EXISTING
SHEET ROCK
FRAMING MEMBERS
REQUIRED FOR
SUPPORT
EXISTING
JOISTS
Fig 4
Fig 5